Methods applied to investigage the major UVCE that occured in the TOTAL refiner's Fluid Catalytic Cracking Unit at La Mède, France - Ineris - Institut national de l'environnement industriel et des risques Access content directly
Conference Papers Year : 1995

Methods applied to investigage the major UVCE that occured in the TOTAL refiner's Fluid Catalytic Cracking Unit at La Mède, France

P. Michaelis
  • Function : Author
A. Hodin
  • Function : Author
P. Mejean
  • Function : Author

Abstract

On monday November 9, 1992 at 5:20 a.m. a major U. V.C.E, occured in the Gas Plant of the TOTAL refinery's Fluid Catalytic Cracking unit at La Mede, France. The origin was a 25 cm2 break in the 8" by-pass of the absorber stripper column cooler; an amount of about 15 tons of LPG and light naphtha was released within 10 minutes, covering an area of 14000m2 including Gas Plant, cryogenic, propene and Merox units before being ignited on the FCC main furnace.
Fichier principal
Vignette du fichier
1995-035_hal.pdf (1.19 Mo) Télécharger le fichier
Origin : Files produced by the author(s)

Dates and versions

ineris-00971929 , version 1 (03-04-2014)

Identifiers

Cite

P. Michaelis, A. Hodin, Jean-François Lechaudel, P. Mejean. Methods applied to investigage the major UVCE that occured in the TOTAL refiner's Fluid Catalytic Cracking Unit at La Mède, France. 8. International Symposium Loss Prevention and Safety Promotion in the Process Industry, Jun 1995, Anvers, France. pp.365-376. ⟨ineris-00971929⟩